The network element expansion subrack cross board is UXCSB, and after replacing it with an XCE board, the service returns to normal.
Products
OptiX OSN3500
Fault category
TU_AIS
T_ALOS
BD_STATUS
WRG_BD_TYPE
Description
Query the single board physical information on the T2000 network manager. the BA2 board position is shown as PQ1 board, and the EGT2 board position is shown as PQ1 board. slot 17 and slot 5 boards are out of position.
TU_AIS, T_ALOS, BD_STATUS, WRG_BD_TYPE alarms are reported on the expansion subrack, but the service is normal.
One week later, the business was affected due to database corruption.
Cause Analysis
Possible causes:
GSCC board failure
Spare board failure in slot 1 where BA2 is located
Device configuration conflict
Failure of the PQ1 board or AUX board of the expansion subrack
Procedure
Confirm the physical slot of the single board on the base station subrack.
Confirm the placement of the veneer in the subrack and the expansion subrack.
Confirm that the expansion subrack is normally powered on.
The expansion subrack's crossover board must be XCE.
Replace the existing crossover board UXCSB of the expansion subrack with the XCE single board.
Query the expansion subrack alarms, the original alarms are lifted, and no new abnormal alarms are added. The service is back to normal.
Reference Information
The expansion subrack does not need to configure the GSCC single board.