OSN3500 cross reporting BUS_ERR,BUS_ERR alarm third parameter is 0x80
| 2025-11-21|Back

Description of the problem

An OSN3500 device connected to a master subrack with an extended subrack cable cross reports BUS_ERR, and the third parameter of the BUS_ERR alarm is 0x80.


Processing

1. Alarm explanation:

A. The third parameter is 0x80, which indicates that the expansion line connected on the cross veneer is not connected.

B, the first parameter may be 0x11, 0x12, 0x13, 0x14. 0x11, 0x12 is the lower DB header cable of the XCE veneer board; 0x13, 0x14 is the upper DB header cable of the XCE veneer board


Root Cause

1、Cable is not connected

2、Bad DB interface of XCS single board

3, XCE single board BD interface bad


Solution

1、Connect the cable

2、Replace the XCS single board

3、Replace XCE single board


The related technical information in this chapter and the troubleshooting process of SDH equipment are collected and organized by Shenzhen Optical Transmission Network Technology Company Limited ( www.opticaltrans.com), please retain the reproduction! Our company specializes in Huawei SDH optical transmission equipment, SDH transmission equipment sales.


Sell Optix OSN3500_Product Quotation_Sales Manufacturer_Product Characteristics_Product Description_Huawei SDH transmission equipment sales
Supply Optix OSN3500_Troubleshooting_Installation and testing_Technical specifications_Technical parameters_Huawei SDH transmission equipment sales

Contact Us
Name:Mr Zhang
Phone:18529092692
Tel:18529092692
Email:info@opticaltrans.com
Address:Cuiguang 1st Distriuct Buiding 8th, Shenzhen, Guangdong Province
Contact
18529092692
Phone:18529092692
Email:info@opticaltrans.com
Address:Cuiguang 1st Distriuct Buiding 8th, Shenzhen, Guangdong Province
Follow Us
Otrans Technology is a high-tech enterprise deeply engaged in optical transmission and network communication equipment, specializing in...
Copyright © 2025 Otrans all right reserve XML 网站模板