Description of the problem
The services of 2 OSN1500 devices in the same cabinet in the current network room have flashed off multiple times at the same time.
Processing
None
root cause
By reviewing the black box records of all the veneers of both devices, it was confirmed that both OSN devices had experienced an instantaneous power-down hard reset at the same time. Since it was both devices in the cabinet that failed, the focus was on the suspicion that it was caused by an abnormal input power supply shared by the two devices. Through the current network investigation, found that the two external input to the PDU power cable installation is not standardized, directly crimped bare wire, and pressure on the insulation skin, resulting in poor contact, resistance is too large, the heat is serious, the terminal insulation skin burnt.
Therefore, the fault for the PDU input cable terminal connection is not standardized, PDU input poor contact, power fluctuations.
Solution
Reconnect the PDU input cable, make sure that the cable is connected tightly, do not press the insulating skin, and recommend the use of cold-pressed terminals
The related technical information in this chapter and the troubleshooting process of SDH equipment are collected and organized by Shenzhen Optical Transmission Network Technology Company Limited ( www.opticaltrans.com), please retain! Our company specializes in Huawei SDH optical transmission equipment, SDH transmission equipment sales.