SDH transmission equipment, if the configuration of the dust net can be cleaned to continue to use the type, you need to regularly clean the dust net to ensure that the equipment normal heat dissipation. If the environment is dusty, increase the frequency of cleaning appropriately, once every two weeks or once a week. During the cleaning process of the dust net, be careful not to pull out the fan when pulling out the dust net.
Models involved
OptiX OSN3500 OptiX OSN 6800 OptiX OSN 3800
Phenomenon Description
In the OptiX OSN 6800 project in a province, several single boards at a site report HARD_BAD alarms, and several services are interrupted. After preliminary analysis, four single boards carrying services have failed.
Cause analysis
There are various reasons for service interruption due to single board failure, and the most likely reasons are as follows:
- Optical module failure causes service interruption.
- Failure of the single-board power module leads to service interruption.
Operation Steps
- After checking the history of alarms for this network element, it is found that the multiple single boards that failed initially reported a TEMP_OVER alarm, and then a HARD_BAD alarm, and then the service was interrupted. On the subrack, the temperatures of the corresponding four single boards were found to be 119°C, 119°C, 82.6°C, and 72.7°C. These four single boards were constantly resetting and could not work normally.
- The OptiX OSN 6800 device is equipped with a fan board, which can automatically adjust the speed to regulate the internal temperature of the device. The fan board was queried to be running at a high speed and the device temperature was still high. It is hypothesized that there is a problem with heat dissipation on this subrack.
- On-site inspection found that the machine room is dusty, the faulty single board where the equipment is covered with dust on the dust net, the air inlet is blocked, poor heat dissipation performance, the faulty single board temperature is very high. According to this judgment, due to the dust net air inlet is blocked by dust, equipment heat dissipation is reduced, resulting in a gradual increase in the operating temperature of the business board, reported TEMP_OVER alarm. As the maintenance personnel did not timely exclude the high temperature alarm, the single board for a long time running at high temperatures, ultimately leading to device burnout business interruption.
References
A summary and recommendations on this case are provided below:
- Maintenance personnel should regularly clean the equipment dust net to ensure that the equipment has better heat dissipation conditions.
- When a single board reports a TEMP_OVER alarm, pay enough attention to it and troubleshoot the problem in time. Consider whether the fan speed is set incorrectly or the dust net air inlet blockage reduces the cooling capacity.
- Clear the alarms on the current network in time.
The related technical information in this chapter and the troubleshooting process of SDH equipment are provided by Shenzhen Optical Transmission Network Technology Co., Ltd (www.opticaltrans.com), please retain the reproduction! Huawei SDH Optical Transmission Equipment,SDH Transmission Equipment Sales